GMTLaminar laminar-flow ceilings for operating theatres

GMTLaminar is Goldmarktech’s own sterile-air ceiling, made in Thailand. HEPA-filtered air leaves through a double fabric membrane as a slow, even downward flow over the operating table. It keeps the wound, the surgeons and nurses and the instrument (back) table in clean air, and carries particles and germs away, lowering airborne contamination and, with it, the risk of infection.

Made in
Thailand, a Goldmarktech product
Shapes
Round, octagonal and rectangular
Standard size
2,400 mm wide, 450 mm high; other sizes to order
Air velocity
0.25–0.27 m/s, unidirectional
Filters
HEPA H13, with a DEHS test connection
Cleanliness
ISO class 5 (EN ISO 14644-1)

How it works

Conditioned air from the air-handling unit enters the GMTLaminar plenum through HEPA H13 filters in gas-tight housings at the side of the unit. From the plenum it passes through a streamlined frame covered on both sides with a special fabric. This double membrane turns it into a slow, even, unidirectional flow of 0.25–0.27 m/s that moves straight down over the protected area.

That steady flow, often called a protective stream, carries particles and germs released at the table away from the wound and towards the room’s return-air grilles, instead of mixing them back into the air above the patient.

Where it is used

  • Operating theatres
  • Clean rooms
  • Laboratories
How GMTLaminar supplies an operating theatre Supply air HEPA H13 filters GMTLaminar membrane Laminar flow 0.25–0.27 m/s Return air Return air Protected area
Section through an operating theatre, not to scale. The dashed lines mark the protected area around the operating table.

Three shapes

The round model has no corners, so air leaves evenly over its whole face, and it needs less air than a cornered shape of the same width.

  • Round

    Diameter
    2,400 mm
    Height
    450 mm
    Air volume
    4,000 m³/h
    Air velocity
    0.25 m/s
  • Octagonal

    Width across flats
    2,400 mm
    Height
    450 mm
    Air volume
    4,600 m³/h
    Air velocity
    0.27 m/s
  • Rectangular

    Size
    2,400 × 1,200–2,400 mm
    Height
    450 mm
    Air volume
    3,700 m³/h
    Air velocity
    0.27 m/s

Standard sizes. Other sizes are made to order.

What it delivers

Clean air at the table
ISO class 5 to EN ISO 14644-1: no more than 3,520 particles of 0.5 µm or larger per cubic metre.
A sterile zone
Designed to keep germs in the sterile area to no more than 10 CFU/m³.
Even air
Air leaves at almost the same speed over the whole face, so the protected area gets a steady, even flow.
Tested in place
A DEHS aerosol connection upstream of the filters lets them be leak-tested at any time, without taking the membrane down.
Easy to disinfect
The plenum is airtight and fully lacquered, and the filter housings stand up to the disinfectants used in hospitals.

What is in the unit

  • Plenum Airtight and fully lacquered, resistant to disinfectants on the inside.
  • Filter housings Gas-tight and resistant to disinfectants, with a duct connection. Their positions are chosen to suit the ceiling.
  • HEPA H13 filters Pleated glass-fibre medium with thread spacers, in a galvanised steel frame with an EPDM gasket.
  • Filter seal and test groove A sealing frame with an integrated test groove, for checking that the filters are tight (DIN 1946-4).
  • Fabric membrane A streamlined aluminium frame covered with fabric on both sides, in large sections that come down from below.
  • Lighting A closed IP65 light with perforated-plate reflectors and built-in electronics.
  • Surgical lights and services Passages for the surgical-light mounting, an equipotential bonding point outside the plenum and a perimeter angle that joins the suspended ceiling.

The filters and the membrane go in only after the theatre’s final clean, just before it is first used.

Made in Thailand

GMTLaminar is our own product and is made in Thailand. Hospitals, designers and contractors deal directly with the company behind it, from selection and installation to service.

Tell us about the theatre, the ceiling and the air-handling unit, and we will help you choose the shape and size.

Talk to an engineer

Tell us about the building and the plant you need to control, and one of our engineers will get back to you.

Phone
+66 2 722 1362
Email
info@goldmarktech.com
LINE
@056vqxls
Office hours
Monday to Friday, 08:00–17:00